Machine Overzicht

Generator events en service beheer USB: 6F2C5318A8 ×
Records
915
van 353,750
Machines
1
Starts
405
Warnings
37
25 resultaten · pagina 36 van 37
Dubbelklik service uren om te bewerken
ID Machine Gebeurtenis Tijd Uren Service Status USB ID
313720 200-038 XASI Engine Stopped 06-10-2025 08:17:15 10,756 500 OVER BEURT URGENT! 6F2C5318A8
313719 200-038 XASI High Coolant Temp Elec Trip Alarm Electrical Trip 06-10-2025 08:16:03 10,756 500 OVER BEURT URGENT! 6F2C5318A8
313715 200-038 XASI High Coolant Temp Warning 06-10-2025 07:56:02 10,756 500 OVER BEURT URGENT! 6F2C5318A8
313704 200-038 XASI kW Overload Alarm Warning 06-10-2025 07:41:05 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313703 200-038 XASI Engine Start 06-10-2025 07:40:03 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313701 200-038 XASI Engine Stopped 06-10-2025 07:39:11 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313702 200-038 XASI Engine Stopped 06-10-2025 07:38:58 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313323 200-038 XASI MSC Failure Warning 02-10-2025 09:26:12 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313318 200-038 XASI Engine Stopped 02-10-2025 09:21:49 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313319 200-038 XASI Negative Phase Sequence Alarm Shutdown 02-10-2025 09:21:38 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313315 200-038 XASI High Coolant Temp Warning 02-10-2025 09:04:00 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313314 200-038 XASI kW Overload Alarm Warning 02-10-2025 08:54:22 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313310 200-038 XASI Engine Start 02-10-2025 08:38:23 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313309 200-038 XASI Engine Stopped 02-10-2025 08:35:21 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313307 200-038 XASI Engine Stopped 02-10-2025 08:34:38 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313308 200-038 XASI Engine Stopped 02-10-2025 08:34:16 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313304 200-038 XASI MSC Failure Warning 02-10-2025 08:24:21 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313294 200-038 XASI MSC Failure Warning 02-10-2025 07:46:14 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313282 200-038 XASI Engine Stopped 02-10-2025 07:27:18 10,755 500 OVER BEURT URGENT! 6F2C5318A8
313276 200-038 XASI MSC Failure Warning 02-10-2025 07:23:25 10,754 500 OVER BEURT URGENT! 6F2C5318A8
313268 200-038 XASI Engine Start 02-10-2025 07:17:00 10,754 500 OVER BEURT URGENT! 6F2C5318A8
313265 200-038 XASI Engine Stopped 02-10-2025 07:01:14 10,754 500 OVER BEURT URGENT! 6F2C5318A8
313263 200-038 XASI Engine Start 02-10-2025 07:00:42 10,754 500 OVER BEURT URGENT! 6F2C5318A8
313260 200-038 XASI MSC ID Error Electrical Trip 02-10-2025 07:00:10 10,754 500 OVER BEURT URGENT! 6F2C5318A8
313259 200-038 XASI MSC ID Error Electrical Trip 02-10-2025 06:59:08 10,754 500 OVER BEURT URGENT! 6F2C5318A8
876–900 van 915